heat transfer enhancement in tubular heat exchanger with double v-ribbed twisted-tapes
Clicks: 184
ID: 258053
2016
An experimental work on heat transfer enhancement in a round tube by insertion of double twisted tapes in common with 30° V-shaped ribs has been conducted. Air as the test fluid flowed through the test tube having a constant wall heat-flux with Reynolds number (Re) from 5300 to 24,000. The combined vortex generators (called “V-ribbed twisted tape”) were obtained by incorporating V-shaped ribs into the edges of double co-twisted tapes having a similar twist ratio of 4. The effect of pertinent V-rib parameters such as four relative rib heights, (called “blockage ratio”, BR=b/D= 0.07, 0.09, 0.14 and 0.19) and a relative rib pitch, (PR=P/D=1.9) at an attack angle of rib, α=30° on thermal characteristics was investigated. The experimental results reveal that the heat transfer and pressure drop in terms of the respective Nusselt number and friction factor for the V-ribbed twisted tapes show the increasing trend with the rise of Re and BR. The V-ribbed twisted tape with BR=0.19 yields the highest heat transfer and friction factor. However, the maximum thermal enhancement factor is about 1.4 for the V-ribbed twisted tape at BR=0.09 but is around 1.09 for the twisted tape with no rib.
Reference Key |
tamna2016caseheat
Use this key to autocite in the manuscript while using
SciMatic Manuscript Manager or Thesis Manager
|
---|---|
Authors | ;Sombat Tamna;Yingyong Kaewkohkiat;Sompol Skullong;Pongjet Promvonge |
Journal | gateways : international journal of community research & engagement |
Year | 2016 |
DOI | 10.1016/j.csite.2016.01.002 |
URL | |
Keywords |
Citations
No citations found. To add a citation, contact the admin at info@scimatic.org
Comments
No comments yet. Be the first to comment on this article.